This is part of a series of articles that demonstrate how to create a runtime application for PLCnext Control. Each article builds on tasks that were completed in earlier articles, so it is recommended to follow the series in sequence.
OPC UA is the industry standard for exchanging non-real-time data between industrial automation software components. It would therefore be useful if data in a PLCnext runtime application could be accessed via an OPC UA server.
An OPC UA server for a custom runtime application could be implemented in a number of ways. However, since there is already a full-featured OPC UA server included with every PLCnext Control, it makes sense to use this OPC UA server for applications running on the same PLC.
This article provides a procedure for the following two tasks:
-
Creating custom data items in the OPC UA server address space.
-
Exchanging data between the runtime and custom data items in the OPC UA server address space.
On a PLCnext Control, the OPC UA server address space is populated by ACF and PLM components and programs. Since the OPC UA server address space cannot be populated directly from a runtime application, we must create a separate shared object library containing an ACF component that defines data items from our runtime application that should appear in the OPC UA server address space. We must then instruct the PLCnext runtime to create the ACF component at startup.
An ACF component that populates the OPC UA address space also creates a GDS port variable for each OPC UA data item that it creates. Each of these GDS port variables is linked to its associated OPC UA data item, so applications that can read and write GDS variables can use these variables to (indirectly) read and write the corresponding OPC UA data items.
The PLCnext Command-Line Interface (CLI) includes a template for an ACF project, so we will use this as the starting point in the creation of an ACF component that we will use to create OPC UA data items and their associated GDS variables.
-
Using the PLCnext CLI, create a new project based on the standard template and set the target for the build. In this example, the project is called
RuntimeOpc
, but you can call it whatever you want.plcncli new acfproject -n RuntimeOpc cd RuntimeOpc plcncli set target --add -n AXCF2152 -v 2022.0
-
Open the Component .hpp file in your favourite editor, and add the following GDS Port definition in the section indicated by the auto-generated comment:
//#attributes(Hidden|Opc) struct DATA { //#attributes(Input) int32 Runtime_RW = 0; //#attributes(Output) int32 Runtime_RO = 0; }; //#port DATA data;
This will create two OPC UA data items; one read/write (Input) and one read-only (Output), each holding a 32 bit integer value. Corresponding GDS variables will also be created using this information.
This
struct
can include any number of elements. The data type of each element must be taken from the C++ column of the "Available data types" table in the PLCnext Info Center. -
Auto-generate the remaining C++ source code for the project. From the root directory of the RuntimeOpc project:
plcncli generate code
-
Build the project. From the root directory of the project:
plcncli build
-
In the project root directory, create a new directory called
data
. -
In the project
.acf.config
file, replace the Library and Component entries with the following:<Library name="RuntimeOpc" binaryPath="../RuntimeOpc/libRuntimeOpc.so" />
<Component name="Runtime" type="RuntimeOpc.RuntimeOpcComponent" library="RuntimeOpc" />
This instructs the PLCnext runtime to create one instance of the RuntimeOpcComponent component, called Runtime, from the RuntimeOpc shared object library that we have just built.
-
Download the application to the PLC. From the project root directory copy the following files:
- Shared object library containing the ACF component.
ssh [email protected] 'mkdir -p projects/RuntimeOpc' scp bin/AXCF2152_22.0.3.129/Release/lib/libRuntimeOpc.so [email protected]:~/projects/RuntimeOpc
- ACF configuration file.
scp src/RuntimeOpcLibrary.acf.config [email protected]:~/projects/Default
-
On the PLC, edit the file
/opt/plcnext/projects/PCWE/Services/OpcUA/PCWE.opcua.config
. In the<GdsPortsToProvide>
section, change the value<None />
to<All />
. That section of the file should then look like:<GdsPortsToProvide> <All /> </GdsPortsToProvide>
-
Restart the PLCnext runtime:
sudo /etc/init.d/plcnext restart
-
In an OPC UA client like UaExpert from Unified Automation:
- In the Address Space pane, open the branch PLCnext -> Runtime
- Add the two new data items to the Data Access View pane.
- Attempt to change the value of both data items. It is not possible to change the value of the Output (read-only) data item.
These OPC UA variables can now be used by the runtime application.
GDS variables corresponding to the new OPC UA data items have been created and are available to any application that can access the Global Data Space. The runtime application can exchange data with these GDS variables using the "Data Access" and/or "Subscription" RSC services.