SIA 2061 #67

Open
Linwal opened this issue Aug 17, 2020 · 2 comments
Open

SIA 2061 #67

Linwal opened this issue Aug 17, 2020 · 2 comments

Comments

@Linwal
Copy link
Collaborator

Linwal commented Aug 17, 2020

Implement SIA 2061 [32] for simplified electrical storage sizing.

--> Check if similar options are available for heat storage.

@kuhnal
Copy link
Collaborator

kuhnal commented Feb 9, 2021

For "Pufferspeicher" (heat-pump systems), there are very simplified calculations available, with XYliter/kW_heatingpower. (https://www.energie-experten.org/heizung/heizungstechnik/pufferspeicher). Storage tanks for domestic hot water can also easily be dimensioned, for example via typical domestic hot water usage per person (around 45l/p/d (--> SIA 385/2, here also a more detailed calculation including losses etc. is available)) and then assuming that the storage tank needs to be able to store enough water for the domestic hot water usage of one day. Of course, for larger buildings (MFH) this does not simply apply, but for a rough estimation this could be enough.

@kuhnal
Copy link
Collaborator

kuhnal commented Feb 11, 2021

"Als Richtwert für die Dimensionierung des technischen Speichers gelten 15 -25 Liter (Seriespeicher) resp. 35 Liter (Parallelspeicher) pro Kilowatt der maximalen Wärmepumpen-Leistung."s.34
Source: EnergieSchweiz (2019), Leistungsgarantie.
2610-EnergieSchweiz-Leistungsgarantie-A4 805.250 D web.pdf