Set DefaultBaseFrequency=60 !! Define frequência de 60Hz
Set Datapath=C:\ODSS\ !! Define o caminho dos arquivos
!! clear
!! Equivalente da subestação
new circuit.example basekV=138 pu=1.0 angle=0 frequency=60 phases=3
!! Transformador da Subestação
new transformer.Sub phases=3 windings=2 buses=(sourcebus, B1)
conns=(delta, wye) kvs=(138, 13.8) kvas=(30000, 30000) %loadloss=0 xhl=10
!! Transformador abaixador
new transformer.TLV phases=3 windings=2 buses=(B2, B3)
conns=(delta, wye) kvs=(13.8, 0.22) kvas=(10000, 10000) %loadloss=0 xhl=5
!! Linha
!! rmatrix = [R11 | R21 R22| R31 R32 R33]
!! xmatrix = [X11 | X21 X22| X31 X32 X33]
!! cmatrix = [C11 | C21 C22| C31 C32 C33]
new linecode.ABC nphases=3 units=km
rmatrix=[ 2.504093 | 0.3798523 2.605409 | 0.3676533 0.3996573 2.517093 ]
xmatrix=[ 1.924003 | 0.35 1.937004 | 0.37 0.40 1.917007 ]
cmatrix=[ 2.8 | -0.6 2.9 | -0.5 -0.7 2.7 ]
new line.lineA-B bus1=B1 bus2=B2 length=2 phases=3 units=km linecode=ABC
!! Carga
new load.CARGAa bus1=B3.1 phases=1 kV=0.127 kW=2000 kvar=640 model=1 conn=wye
new load.CARGAb bus1=B3.2 phases=1 kV=0.127 kW=1000 kvar=330 model=1 conn=wye
new load.CARGAc bus1=B3.3 phases=1 kV=0.127 kW=1500 kvar=540 model=1 conn=wye
!! Capacitor
new Capacitor.Cp bus1=B2 phases=3 kV=13.8 kvar=5000
set voltagebases=[138 13.8 0.22]
calcVoltageBases
set controlmode=static
set mode=snapshot
solve