Modbus

The go-eCharger has a Modbus TCP Interface an which can be used to read some power and energy values. This interface has to be enabled from the app or the http API. Data can be read with the Modbus function 3 and the Modbus function 4. Data can be written with the Modbus function 16. After enabling the tcp port 502 is used.

Function No Name Supported?
01 Read Coil Status No
02 Read Input Status No
03 Read Holding Registers Yes, for all registers listed below
04 Read Input Registers Yes, for all registers listed below
05 Force Single Coil No
06 Preset Single Register No
15 Force Multiple Coils No
16 Preset Multiple Registers Yes, for all registers listed below

Using the App to enable and verify the Modbus interface

Tap the tab "Internet" at the bottom, then click on "Advanced Settings" in the menu, then at the very bottom "Modbus"

Using the http API to enable and verify the Modbus interface

The chargers provide api keys to configure and verify the modbus interface. These api keys can be used with the http api.

Example: http://192.168.0.77/api/set?men=true

api key description datatype R?W? Category
men modbus slave enabled bool R/W Config
msp modbus slave port (requires reboot) uint16 R/W Config
msb modbus slave swap bytes bool R/W Config
msr modbus slave swap registers bool R/W Config
mro modbus slave read operations size_t R Status
mwo modbus slave write operations size_t R Status

Modbus Profile

Holding Registers (read/write)

Data in this table can be read with modbus function 03 and written with modbus function 16.

Register (wire-format) Name Register Type Data type Lenght Description
40201 (200) ALLOW Holding Register uint16_t 1 allow_charging: PWM Signal is allowed
to abut
0: no
1: yes
40202 (201) ACCESS_STATE Holding Register uint16_t 1 access_state: access control.
0: open
1: RFID / App needed
2: electricity price / automatic
3: scheduler
40205 (204) CABLE_LOCK_MODE Holding Register uint16_t 1 Cable lock setting
0: Lock while the car is connected
1: Unlock automatically after
charging
2: Always keep the cable locked
40207 (206) LED_BRIGHTNESS Holding Register uint16_t 1 LED brightness from 0-255
0: LED off
255: LED brightness max
40208 (207) LED_SAVE_ENERGY Holding Register uint16_t 1 led_save_energy: LED switch off
automatically after 10 seconds
0: Energy saving function deactivated
1: Energy saving function activated
40209 (208) ELECTRICITY_PRICES_HOURS Holding Register uint16_t 1 Minimum count ​of hours that must be
charged with "Electricity price - automatic"
Example: 2 ("Car is full enough after 2 hours")
40210 (209) ELECTRICITY_PRICES_FINISHED Holding Register uint16_t 1 Hour (​time) in which with "electricity price
- automatic" the charge must have lasted
at least aho hours.
Example: 7 ("Ready by 7:00, so charged at
least 2 hours before that")
40211 (210) ELECTRICITY_PRICES_ZONE Holding Register uint16_t 1 Awattar price zone
0: Austria
1: Germany
40212 (211) AMPERE_MAX Holding Register uint16_t 1 Absolute Max Amps: Maximum
value for Amps setting
Example: 20 (setting to more than
20A in the app not possible)
40213 (212) AMPERE_L1 Holding Register uint16_t 1 Ampere level 1 for push button on the
device.
6-32: Ampere level activated
0: Level deactivated (will be skipped)
40214 (213) AMPERE_L2 Holding Register uint16_t 1 Ampere level 2 for push button on the
device.
6-32: Ampere level activated
0: Level deactivated (will be skipped)
40215 (214) AMPERE_L3 Holding Register uint16_t 1 Ampere level 3 for push button on the
device.
6-32: Ampere level activated
0: Level deactivated (will be skipped)
40216 (215) AMPERE_L4 Holding Register uint16_t 1 Ampere level 4 for push button on the
device.
6-32: Ampere level activated
0: Level deactivated (will be skipped)
40217 (216) AMPERE_L5 Holding Register uint16_t 1 Ampere level 5 for push button on the
device.
6-32: Ampere level activated
0: Level deactivated (will be skipped)
40218 (217) CLOUD_DISABLED Holding Register uint16_t 1 Cloud disabled
0: cloud enabled
1: cloud disabled
40219 (218) NORWAY_MODE Holding Register uint16_t 1 Norway mode​ activated
0: deactivated (ground detection
activated)
1: activated (no ground detection,
only intended for IT networks)
40300 (299) AMPERE_VOLATILE Holding Register uint16_t 1 Amps Value for the PWM
signaling in whole amps of
6-32A

Is not saved in the EEPROM
and is reset to the value last saved in the EEPROM during the next boot process.

For energy control
40301 (300) AMPERE_EEPROM Holding Register uint16_t 1 Amps Value for the PWM
signaling in whole amps of
6-32A

Is saved in the EEPROM (max.
write cycles approx. 100, 000)
40333 (332) PHASE_SWITCH_MODE Holding Register uint16_t 1 Same as api key psm, only accepts values 0, 1, 2 (Since Firmware 55.5)
40334 (333)
30335 (334)
30336 (335)
30337 (336)
ENERGY_LIMIT Holding Register float64 4 Same as api key dwo, set to float Inf to express "null" limit (disabled limit), or any other float in watthours (Wh) (Since Firmware 55.5)
40338 (337) FORCE_STATE Holding Register uint16_t 1 Same as api key frc, only accepts values 0, 1, 2 (Since Firmware 55.6)

Input Registers (read-only)

Data in this table can be read with modbus function 04.

Register(wire-format) Name Register Type Data type Lenght Description
30101 (100) CAR_STATE Input Register uint16_t 1 Status PWM signaling
0: Unknown, Charging station defective
1: Charging station ready, no car
2: Car is charging
3: Waiting for car
4: Charging finnished, Car still connected
30102 (101) PP_CABLE Input Register uint16_t 1 Type2 Cable ampere coding
13-32: ampere coding
0: no cable
30106 (105)
30107 (106)
FWV Input Register ascii (4 byte) 2 Firmware version as ASCII
30108 (107) ERROR Input Register uint16_t 1 error:
1: RCCB (Residual current circuit breaker)
3: PHASE (phase disturbance)
8: NO_GROUND (Ground detection)
10, default: INTERNAL (Others)
30109 (108)
30110 (109)
VOLT_L1 Input Register uint32_t 2 Voltage on L1 in volts
30111 (110)
30112 (111)
VOLT_L2 Input Register uint32_t 2 Voltage on L2 in volts
30113 (112)
30114 (113)
VOLT_L3 Input Register uint32_t 2 Voltage on L3 in volts
30115 (114)
30116 (115)
AMP_L1 Input Register uint32_t 2 Amps on L1 in 0.1A (123 equals 12, 3A)
30117 (116)
30118 (117)
AMP_L2 Input Register uint32_t 2 Amps on L2 in 0.1A (123 equals 12, 3A)
30119 (118)
30120 (119)
AMP_L3 Input Register uint32_t 2 Amps on L3 in 0.1A (123 equals 12, 3A)
30121 (120)
30122 (121)
POWER_TOTAL Input Register uint32_t 2 Total power in 0.01W (360000 corresponds to 3.6kW)
30129 (128)
30130 (129)
ENERGY_TOTAL Input Register uint32_t 2 Total amount of energy charged in 0.1kWh (360 corresponds to 36kWh)
132
133
ENERGY_CHARGE Input Register uint32_t 2 Amount of energy charged in
Deka-Watt-Seconds
Example: 100, 000 means 1, 000, 000
Ws (= 277Wh = 0.277kWh) were loaded in this charging process.
144
145
VOLT_N Input Register uint32_t 2 Voltage on N in volts
146
147
POWER_L1 Input Register uint32_t 2 Power on L1 in 0.1kW (36 corresponds to 3.6kW)
148
149
POWER_L2 Input Register uint32_t 2 Power on L2 in 0.1kW (36 corresponds to 3.6kW)
150
151
POWER_L3 Input Register uint32_t 2 Power on L3 in 0.1kW (36 corresponds to 3.6kW)
152
153
POWER_FACTOR_L1 Input Register uint32_t 2 Power factor on L1 in %
154
155
POWER_FACTOR_L2 Input Register uint32_t 2 Power factor on L2 in %
156
157
POWER_FACTOR_L3 Input Register uint32_t 2 Power factor on L3 in %
158
159
POWER_FACTOR_N Input Register uint32_t 2 Power factor on N in %
200 ALLOW Input Register uint16_t 1 allow_charging: PWM Signal is allowed
to abut
0: no
1: yes
202 ADAPTER_INPUT Input Register uint16_t 1 adapter_in: The charging box
is connected with an adapter
0: NO_ADAPTER
1: 16A_ADAPTER
203 UNLOCKED_BY Input Register uint16_t 1 Number of the RFID card that
activated the current charging process
205 PHASES Input Register uint16_t 1 Phases before and after the contactor
binary flags: 0b00ABCDEF
A... phase 3, before the contactor
B... phase 2 before the contactor
C... phase 1 before the contatctor
D... phase 3 after the contactor
E... phase 2 after the contactor
F... phase 1 after the contactor
pha 0b00001000: Phase 1 is
available
pha 0b00111000: Phase1-3 is
available
301
302
303
MAC Input Register char[6] 3 MAC address of the WLAN station, binary
304
305
306
307
308
309
SNR Input Register ascii (12 byte) 6 Serial number of the go-eCharger, as
ASCII
310
311
312
313
314
HOSTNAME Input Register ascii (12 byte) 6 Host name of the go-eCharger, as ASCII
315
316
317
318
IP Input Register ascii (8 byte) 4 IP address of the go-eCharger, 1 byte per register
319
320
321
322
SUBNET Input Register unsigned integer (64) 4 Subnet mask of the go-eCharger, 1
byte per register
30324 (323)
30325 (324)
30326 (325)
30327 (326)
GATEWAY Input Register ascii (4 byte) 4 Go-eCharger gateway, 1 byte per register
30328 (327)
30329 (328)
30330 (329)
30331 (330)
30332 (331)
RFID_CARD Input Register binary (10 byte) 5 Last scanned RFID serial number, 4-byte and 7-byte long numbers will be filled with zeros at the end, 10-byte numbers already fill the 5 modbus register on its own (Since Firmware 55.5)
30333 (332)
30334 (333)
30335 (334)
30336 (335)
ENERGY_CARD0 Input Register double 4 Energy on RFID Card 1 (in W)
30337 (336)
30338 (337)
30339 (338)
30340 (339)
ENERGY_CARD1 Input Register double 4 Energy on RFID Card 2 (in W)
30341 (340)
30342 (341)
30343 (342)
30344 (343)
ENERGY_CARD2 Input Register double 4 Energy on RFID Card 3 (in W)
30345 (344)
30346 (345)
30347 (346)
30348 (347)
ENERGY_CARD3 Input Register double 4 Energy on RFID Card 4 (in W)
30349 (348)
30350 (349)
30351 (350)
30352 (351)
ENERGY_CARD4 Input Register double 4 Energy on RFID Card 5 (in W)
30353 (352)
30354 (353)
30355 (354)
30356 (355)
ENERGY_CARD5 Input Register double 4 Energy on RFID Card 6 (in W)
30357 (356)
30358 (357)
30359 (358)
30360 (359)
ENERGY_CARD6 Input Register double 4 Energy on RFID Card 7 (in W)
30361 (360)
30362 (361)
30363 (362)
30364 (363)
ENERGY_CARD7 Input Register double 4 Energy on RFID Card 8 (in W)
30365 (364)
30366 (365)
30367 (366)
30368 (367)
ENERGY_CARD8 Input Register double 4 Energy on RFID Card 9 (in W)
30369 (368)
30370 (369)
30371 (370)
30372 (371)
ENERGY_CARD9 Input Register double 4 Energy on RFID Card 10 (in W)