Inputs & Feeds

This document gives a brief explanation about how the data is collected and processed by the application, and which inputs and feeds it requires. They must exist in emoncms (for each user), otherwise EWatcher may not work properly. Although not every input and feed defined here is currently being used, but it may be in future versions, so it is advised to have all defined. Luckily enough, there has also been created another module to aid with the definition of the inputs and feeds in a fully automatic way (see here).

This application works with two different types of facilities: electric ones and PV self-consumption ones.

Electric facilities

Inputs

Input Description Units
iload Consumption intensity A
pload Consumption power W
voltage Voltage V

Note: every input is sent, by convention, to the node 7

Feeds

Feed Description Units Type Engine Formula
sILoad Consumption intensity A REALTIME PHPFIWA Log iload
sPLoad Consumption power W REALTIME PHPFIWA Log pload
sVoltage Voltage V REALTIME PHPFIWA Log voltage
eDLoad Daily consumption kWh DAILY PHPTIMESERIES From sPLoad using Power to kWh/d
tLoad Total consumption kWh REALTIME PHPFINA From sPLoad using Power to kWh

PV self-consumption facilities

Inputs

Input Description Units
ipv Photovoltaic intensity A
ppv Photovoltaic power W
iload Consumption intensity A
pload Consumption power W
voltage Voltage V

Note: every input is sent, by convention, to the node 7

Feeds

Feed Description Units Type Engine Formula
sIPv PV intensity A REALTIME PHPFIWA Log ipv
sPPv PV power W REALTIME PHPFIWA Log ppv
sILoad Consumption intensity A REALTIME PHPFIWA Log iload
sPLoad Consumption power W REALTIME PHPFIWA Log pload
sVoltage Voltage V REALTIME PHPFIWA Log voltage
iPvToLoad PV power consumption W REALTIME PHPFIWA ppv if ppv < pload otherwise pload
iGridToLoad Grid power consumption W REALTIME PHPFIWA pload - iPvToLoad
iPLoadFromPv Percentage of consumption with PV power % REALTIME PHPFIWA 100 * iPvToLoad / pload
iPLoadFromGrid Percentage of consumption with grid power % REALTIME PHPFIWA 100 * iGridToLoad / pload (must match 100 - iPLoadFromPv)
iPvToGrid PV power exported to the grid W REALTIME PHPFIWA ppv - iPvToLoad
eDPv Daily PV energy produced kWh DAILY PHPTIMESERIES From sPPv using Power to kWh/d
eDGrid Daily energy imported from the grid kWh DAILY PHPTIMESERIES From iGridToLoad using Power to kWh/d
eDLoad Daily consumption kWh DAILY PHPTIMESERIES From sPLoad using Power to kWh/d
eDPvToGrid Daily PV energy exported to the grid kWh DAILY PHPTIMESERIES From iPvToGrid using Power to kWh/d
dPSelf Percentage of daily self-consumption % DAILY PHPFIWA 100 * (eDPv - eDPvToGrid)/eDPv
dPLoadFromPv Percentage of daily consumption with PV origin % DAILY PHPFIWA 100 * (eDPv - eDPvToGrid) / eDLoad
eDLoadFromPv Daily energy consumption from PV energy kWh DAILY PHPTIMESERIES eDPv - eDPvToGrid
tLoad Total consumption kWh REALTIME PHPFINA From sPLoad using Power to kWh
tPv Total PV energy produced kWh REALTIME PHPFINA From sPPv using Power to kWh
tLoadFromGrid Total energy imported from the grid kWh REALTIME PHPFINA From iGridToLoad using Power to kWh
tPvToLoad Total PV energy consumed kWh REALTIME PHPFINA From iPvToLoad using Power to kWh
tPvToGrid Total PV energy exported to the grid kWh REALTIME PHPFINA tPv - tPvToLoad

Note: the processes Power to kWh and Power to kWh/d do an automatic log of the result

The following values are calculated with JavaScript in the client, so there is no need to create feeds for them:

Var Description Units Type Formula
cGrid Cost of the imported energy units REALTIME cIn * tLoadFromGrid
cPvToGrid Cost of the energy exported to the grid units REALTIME cOut * tPvToGrid
cLoadNoPv Consumption cost without PV units REALTIME cIn * tLoad
cLoadPv Consumption cost with PV units REALTIME cGrid - cPvToGrid
savings Estimated savings units REALTIME cLoadNoPv - cLoadPv

The default values for the configuration settings (you can change them in some of the EWatcher panels) are:

  • cIn = 0.1244
  • cOut = 0.054
  • units = euros