layout | title |
---|---|
documentation |
A8-9 - ZWave |
{% include base.html %}
This describes the Z-Wave device A8-9, manufactured by McoHome Technology Co., Ltd with the thing type UID of mcohome_a8co2_00_000
.
The device is in the category of Sensor, defining Device used to measure something.
The A8-9 supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.
MCOHome A8-9 is a Z-Wave enabled multiple environmental monitoring sensors, with 3.5 inch TFT
clear display and compliant to Z-Wave Plus standard. It is built in with Temperature, Humidity,
PM2.5, CO2, VOC, PIR, illumination, Noise, Smoke sensors. Device can be added into any Z-Wave
network, and is compatible with any other Z-Wave certified devices.
- Temperature: 0 °C ~ 50 °C
- Humidity: 0% RH ~ 99% RH
- PM2.5: 0 µg / m3 ~ 500 µg / m3
- CO2: 0 ppm ~ 5000 ppm
- VOC: 0 ppb - 64000 ppb
- Illumination: 0 Lux ~ 40000 Lux
- Noise: 30 dB ~ 100 dB
- PIR: 0 or 1 detection angle up to 120°
- Smoke: 0 or 1
Specification
- Dimension: 110 * 110 * 32 mm
- Self-dissipation: < 3 Watt
- Hole Pitch: 60 mm or 82 mm
- Work environment: -20 °C ~ + 60 °C < 99% RH (non-condensation)
- Housing: Tempered glass + PC Alloy
- Installation: Wall-mounted (vertical)
Command Class supported by the device: (Supports S2 unauthenticated level)
- COMMAND_CLASS_VERSION
- COMMAND_CLASS_MANUFACTURER_SPECIFIC
- COMMAND_CLASS_DEVICE_RESET_LOCALLY
- COMMAND_CLASS_POWERLEVEL
- COMMAND_CLASS_ASSOCIATION
- COMMAND_CLASS_ASSOCIATION_GRP_INFO
- COMMAND_CLASS_CONFIGURATION
- COMMAND_CLASS_SENSOR_MULTILEVEL
- COMMAND_CLASS_FIRMWARE_UPDATE_MD
Command Class supported by the device: (Not supporting S2)
- COMMAND_CLASS_ZWAVEPLUS_INFO
- COMMAND_CLASS_TRANSPORT_SERVICE_V2
- COMMAND_CLASS_SECURITY_2
- COMMAND_CLASS_SUPERVISION
Note: A Security Enabled Z-Wave Controller must be used in order to fully utilise the product
Add to Z-Wave network
- Activate inclusion mode in the gateway. When device is powered on, hold F1 to select the interface for Z-Wave network inclusion.
- Click F2 five times until turns blue.
- Hold F2 and the device enters into learning mode, then turns blue and the device is added into Z-Wave network.
Remove from Z-Wave network
- Activate exclusion mode in the gateway. When device is powered on, hold F1 to select the interface for Z-Wave network exclusion.
- Click F2 five times until turns blue.
- Hold F2 and the device enters into learning mode, then turns blue and the device is added into Z-Wave network.
Power On / Power Off
Wire the adapter and the device is powered on. It will display all detected information by the sensors.
Display Interface
Hold Key F1 can switch among the following 4 display interfaces:
- Data detecting: display all sensors’ data
- Network: Z-Wave Add/Remove
- Data calibration: to calibrate the detected data manually
- Local time setting
Restore Factory Setting
- Press & hold F1 to enter Z-Wave setting interface, then press & hold F1 again to enter parameters
setting interface; - Press & hold F2 to enter setting interface and select “default”;
- Click F2 3 times and displays “OFF”-->“ON”-->“OK”-->“OFF”, factory setting is restored.
Note: Please use this procedure only when the network primary controller is missing or otherwise inoperable.
Data Calibration
Hold F1 to choose interface for data calibration. Then hold F2 to switch among the sensors. Choose one and click F2, F1 to change the data. After finished, hold F1 can return data detecting interface.
Local Time Setting
Hold F1 to choose interface for local time setting. Then hold F2 to switch among “Hour-Minute-Second-Year-Month-Date”. Click F2, F1 can change the data of flashing item. After finished, hold F1 can return data detecting interface.
The following table summarises the channels available for the A8-9 -:
Channel Name | Channel ID | Channel Type | Category | Item Type |
---|---|---|---|---|
Smoke Alarm Sensor | alarm_smoke | alarm_smoke | Smoke | Switch |
Relative Humidity Sensor | sensor_relhumidity | sensor_relhumidity | Humidity | Number |
Luminance Sensor | sensor_luminance | sensor_luminance | Number | |
Temperature Sensor | sensor_temperature | sensor_temperature | Temperature | Number:Temperature |
Carbon Dioxide (CO2) Sensor | sensor_co2 | sensor_co2 | CarbonDioxide | Number |
Volatile Organic Compound (VOC) Sensor | sensor_voc | sensor_voc | ||
Loudness Sensor | sensor_loudness | sensor_loudness | ||
Particulate Matter (PM2.5) Sensor | sensor_particulate | sensor_particulate | Number | |
PIR Motion Sensor | alarm_motion | alarm_motion | Motion | Switch |
Indicates if a smoke is triggered.
The alarm_smoke
channel is of type alarm_smoke
and supports the Switch
item and is in the Smoke
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Indicates the current relative humidity.
The sensor_relhumidity
channel is of type sensor_relhumidity
and supports the Number
item and is in the Humidity
category. This is a read only channel so will only be updated following state changes from the device.
Indicates the current light reading.
The sensor_luminance
channel is of type sensor_luminance
and supports the Number
item. This is a read only channel so will only be updated following state changes from the device.
Indicates the current temperature.
The sensor_temperature
channel is of type sensor_temperature
and supports the Number:Temperature
item and is in the Temperature
category.
Indicates the CO2 level.
The sensor_co2
channel is of type sensor_co2
and supports the Number
item and is in the CarbonDioxide
category. This is a read only channel so will only be updated following state changes from the device.
Channel type information on this channel is not found.
Channel type information on this channel is not found.
Indicates the level of particulate matter.
The sensor_particulate
channel is of type sensor_particulate
and supports the Number
item. This is a read only channel so will only be updated following state changes from the device.
Indicates if a motion alarm is triggered.
The alarm_motion
channel is of type alarm_motion
and supports the Switch
item and is in the Motion
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
The following table provides a summary of the 27 configuration parameters available in the A8-9. Detailed information on each parameter can be found in the sections below.
Param | Name | Description |
---|---|---|
1 | PM25 Delta Level | =0 Turn off report |
2 | CO2 Delta Level | =0 Turn off report |
3 | Temperature Delta Level | =0 Turn off report |
4 | Humidity Delta Level | =0 Turn off report |
5 | VOC Delta Level | =0 Turn off report |
6 | Lux Delta Level | =0 Turn off report |
7 | dB Delta Level | =0 Turn off report |
8 | PIR Motion Sensor Reporting | =0 Turn off report |
9 | Smoke Sensor Reporting | =0 Turn off report |
10 | Smoke Timer | =0 Turn off report |
11 | PIR Timer | =0 Turn off report |
12 | PM2.5 Timer | =0 Turn off report >=35 Report every interval n * 1 s |
13 | CO2 Timer | =0 Turn off report >=35 Report every interval n * 1 s |
14 | Temperature Timer | =0 Turn off report >=35 Report every interval n * 1 s |
15 | Humidity Timer | =0 Turn off report >=35 Report every interval n * 1 s |
16 | VOC Timer | =0 Turn off report >=35 Report every interval n * 1 s |
17 | Lux Timer | =0 Turn off report >=35 Report every interval n * 1 s |
18 | dB Timer | =0 Turn off report >=35 Report every interval n * 1 s |
47 | Temperature Unit | Select Celsius or Fahrenheit |
50 | T_Offset | -10.0 °C ~ 10.0 °C |
51 | RH_OffSet | -20% ~ 20% |
52 | CO2_OffSet | -500 ~ 500 ppm |
53 | PM2.5_OffSet | -100 ~ 100 µg/m3 |
54 | Lux_OffSet | -5000 ~ 5000 lux |
55 | VOC_Correct | -100 ~ 100 |
56 | dB_Correct | -50 ~ 50 |
255 | Restore | Restore factory settings (0x55/85) or default parameters (0xAA/170) |
=0 Turn off report | >=2 Report when change > n * 1 µg / m3
Values in the range 0 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_1_1
and is of type INTEGER
.
=0 Turn off report | >=1 Report when change > n * 5 ppm
Values in the range 0 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_2_1
and is of type INTEGER
.
=0 Turn off report | >=1 Report when change > n * 0.5 °C
Values in the range 0 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_3_1
and is of type INTEGER
.
=0 Turn off report | >=1 Report when change > n %
Values in the range 0 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_4_1
and is of type INTEGER
.
=0 Turn off report | >=1 Report when change > n * 5 ppb
Values in the range 0 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_5_1
and is of type INTEGER
.
=0 Turn off report | >=1 Report when change > n * 1 Lux
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_6_2
and is of type INTEGER
.
=0 Turn off report | >=1 Report when change > n * 1 dB
Values in the range 0 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_7_1
and is of type INTEGER
.
=0 Turn off report | =1 Report change
The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | Turn off report |
1 | Report change |
The manufacturer defined default value is 0
(Turn off report).
This parameter has the configuration ID config_8_1
and is of type INTEGER
.
=0 Turn off report | =1 Report change
The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | Turn off report |
1 | Report change |
The manufacturer defined default value is 1
(Report change).
This parameter has the configuration ID config_9_1
and is of type INTEGER
.
=0 Turn off report | >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_10_2
and is of type INTEGER
.
=0 Turn off report | >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_11_2
and is of type INTEGER
.
=0 Turn off report >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_12_2
and is of type INTEGER
.
=0 Turn off report >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_13_2
and is of type INTEGER
.
=0 Turn off report >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_14_2
and is of type INTEGER
.
=0 Turn off report >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_15_2
and is of type INTEGER
.
=0 Turn off report >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_16_2
and is of type INTEGER
.
=0 Turn off report >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_17_2
and is of type INTEGER
.
=0 Turn off report >=35 Report every interval n * 1 s
Values in the range 0 to 32767 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_18_2
and is of type INTEGER
.
Select Celsius or Fahrenheit
The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | °C |
1 | °F |
The manufacturer defined default value is 0
(°C).
This parameter has the configuration ID config_47_1
and is of type INTEGER
.
-10.0 °C ~ 10.0 °C
Values in the range -128 to 127 may be set.
The manufacturer defined default value is 100
.
This parameter has the configuration ID config_50_1
and is of type INTEGER
.
-20% ~ 20%
Values in the range 0 to 40 may be set.
The manufacturer defined default value is 20
.
This parameter has the configuration ID config_51_1
and is of type INTEGER
.
-500 ~ 500 ppm
Values in the range 0 to 1000 may be set.
The manufacturer defined default value is 500
.
This parameter has the configuration ID config_52_2
and is of type INTEGER
.
-100 ~ 100 µg/m3
Values in the range -128 to 127 may be set.
The manufacturer defined default value is 100
.
This parameter has the configuration ID config_53_1
and is of type INTEGER
.
-5000 ~ 5000 lux
Values in the range 0 to 10000 may be set.
The manufacturer defined default value is 5000
.
This parameter has the configuration ID config_54_2
and is of type INTEGER
.
-100 ~ 100
Values in the range -128 to 127 may be set.
The manufacturer defined default value is 100
.
This parameter has the configuration ID config_55_1
and is of type INTEGER
.
-50 ~ 50
Values in the range 0 to 100 may be set.
The manufacturer defined default value is 50
.
This parameter has the configuration ID config_56_1
and is of type INTEGER
.
Restore factory settings (0x55/85) or default parameters (0xAA/170)
The following option values may be configured -:
Value | Description |
---|---|
85 | Restore factory settings |
170 | Restore default parameters |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_255_1_wo
and is of type INTEGER
.
This is a write only parameter.
Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.
The A8-9 supports 1 association group.
The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation.
Association group 1 supports 1 node.
Command Class | Comment |
---|---|
COMMAND_CLASS_NO_OPERATION_V1 | |
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SENSOR_MULTILEVEL_V10 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_CONFIGURATION_V1 | |
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1 | |
COMMAND_CLASS_POWERLEVEL_V1 | |
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_VERSION_V2 | |
COMMAND_CLASS_ENERGY_PRODUCTION_V1 | |
COMMAND_CLASS_SECURITY_V1 |
Command Class | Comment |
---|
Did you spot an error in the above definition or want to improve the content? You can contribute to the database here.