16 |
CN_UINT8 |
Device state |
0=init, 1=normal, 2=filterwizard, 3=commissioning, 4=supplierfactory, 5=zehnderfactory, 6=standby, 7=away, 8=DFC |
17 |
CN_UINT8 |
?? ROOM_T10 |
|
18 |
CN_UINT8 |
Changing filters |
1=active, 2=changing filter |
33 |
CN_UINT8 |
?? Preset |
0, 1 |
35 |
CN_UINT8 |
?? Temperature Profile |
1 |
36 |
CN_UINT8 |
?? STANDBY |
|
37 |
CN_UINT8 |
|
0 |
40 |
CN_UINT8 |
?? MANUALMODE |
|
42 |
CN_UINT8 |
|
0 |
49 |
CN_UINT8 |
Operating mode |
-1=auto, 1=limited manual, 5=unlimited manual, 6=boost |
50 |
CN_UINT8 |
?? Bypass |
|
51 |
CN_UINT8 |
?? Temperature Profile |
|
52 |
CN_UINT8 |
?? STANDBY |
|
53 |
CN_UINT8 |
?? COMFOCOOLOFF |
-1, 0, 1 |
54 |
CN_UINT8 |
Supply Fan Mode |
-1=balanced, 1=supply only |
55 |
CN_UINT8 |
Exhaust Fan Mode |
-1=balanced, 1=exhaust only |
56 |
CN_UINT8 |
Manual Mode |
-1=auto, 1=unlimited manual |
57 |
CN_UINT8 |
|
-1, 0 |
58 |
CN_UINT8 |
|
-1, 0 |
65 |
CN_UINT8 |
Fans: Fan speed setting |
0=away, 1=low, 2=medium, 3=high |
66 |
CN_UINT8 |
Bypass activation mode |
0=auto, 1=full, 2=none |
67 |
CN_UINT8 |
Temperature Profile |
0=normal, 1=cold, 2=warm |
68 |
CN_UINT8 |
?? STANDBY |
0 |
69 |
|
?? COMFOCOOLOFF |
0=auto, 1=off |
70 |
CN_UINT8 |
Supply Fan Mode |
0=balanced, 1=supply only |
71 |
CN_UINT8 |
Exhaust Fan Mode |
0=balanced, 1=exhaust only |
72 |
CN_UINT8 |
?? MANUALMODE |
|
73 |
CN_UINT8 |
|
0 |
74 |
CN_UINT8 |
|
0 |
81 |
CN_UINT32 |
Fan Speed Next Change |
-1=no change, else countdown in seconds |
82 |
CN_UINT32 |
Bypass Next Change |
-1=no change, else countdown in seconds |
85 |
CN_UINT32 |
ComfoCool Next Change |
-1=no change, else countdown in seconds |
86 |
CN_UINT32 |
Supply Fan Next Change |
-1=no change, else countdown in seconds |
87 |
CN_UINT32 |
Exhaust Fan Next Change |
-1=no change, else countdown in seconds |
88 |
CN_UINT32 |
?? MANUALMODE |
|
89 |
CN_UINT32 |
|
-1, 0 |
90 |
CN_UINT32 |
|
-1, 0 |
96 |
CN_BOOL |
|
|
115 |
CN_BOOL |
?? EXHAUST_F12 |
|
116 |
CN_BOOL |
?? SUPPLY_F22 |
|
117 |
CN_UINT8 |
Fans: Exhaust fan duty |
value in % (28%) |
118 |
CN_UINT8 |
Fans: Supply fan duty |
value in % (29%) |
119 |
CN_UINT16 |
Fans: Exhaust fan flow |
value in m³/h (110 m³/h) |
120 |
CN_UINT16 |
Fans: Supply fan flow |
value in m³/h (105 m³/h |
121 |
CN_UINT16 |
Fans: Exhaust fan speed |
value in rpm (1069 rpm) |
122 |
CN_UINT16 |
Fans: Supply fan speed |
value in rpm (1113 rpm) |
128 |
CN_UINT16 |
Power Consumption: Current Ventilation |
value in Watt (15 W) |
129 |
CN_UINT16 |
Power Consumption: Total year-to-date |
value in kWh (23 kWh) |
130 |
CN_UINT16 |
Power Consumption: Total from start |
value in kWh (23 kWh) |
144 |
CN_UINT16 |
Preheater Power Consumption: Total year-to-date |
value in kWh (23 kWh) |
145 |
CN_UINT16 |
Preheater Power Consumption: Total from start |
value in kWh (23 kWh) |
146 |
CN_UINT16 |
Preheater Power Consumption: Current Ventilation |
value in Watt (15 W) |
176 |
CN_UINT8 |
RF Pairing Mode |
0=not running, 1=running, 2=done, 3=failed, 4=aborted |
192 |
CN_UINT16 |
Days left before filters must be replaced |
value in days (130 days) |
208 |
CN_UINT8 |
Device Temperature Unit |
0=celsius, 1=farenheit |
209 |
CN_INT16 |
Running Mean Outdoor Temperature (RMOT) |
value in °C (117 -> 11.7 °C) |
210 |
CN_BOOL |
Heating Season is active |
0=inactive, 1=active |
211 |
CN_BOOL |
Cooling Season is active |
0=inactive, 1=active |
212 |
CN_UINT8 |
Temperature profile target |
value in °C (238 -> 23.8 °C) |
213 |
CN_UINT16 |
Avoided Heating: Avoided actual |
value in Watt (441 -> 4.41 W) |
214 |
CN_UINT16 |
Avoided Heating: Avoided year-to-date |
value in kWh (477 kWh) |
215 |
CN_UINT16 |
Avoided Heating: Avoided total |
value in kWh (477 kWh) |
216 |
CN_UINT16 |
Avoided Cooling: Avoided actual |
value in Watt (441 -> 4.41 W) |
217 |
CN_UINT16 |
Avoided Cooling: Avoided year-to-date |
value in kWh (477 kWh) |
218 |
CN_UINT16 |
Avoided Cooling: Avoided total |
value in kWh (477 kWh) |
219 |
CN_UINT16 |
|
0 |
220 |
CN_INT16 |
?? Outdoor Air Temperature (Preheated) |
value in °C (75 -> 7.5 °C) |
221 |
CN_INT16 |
?? Temperature: Supply Air (PostHeated) |
value in °C (170 -> 17.0 °C) |
224 |
CN_UINT8 |
Device Airflow Unit |
1=kg/h, 2=l/s, 3=m³/h |
225 |
CN_UINT8 |
Sensor based ventilation mode |
0=disabled, 1=active, 2=overruling |
226 |
CN_UINT16 |
Fan Speed (modulated) |
0, 100, 200, 300 (0-300 when modulating and PDO 225=2) |
227 |
CN_UINT8 |
Bypass state |
value in % (100% = fully open) |
228 |
CN_UINT8 |
?? FrostProtectionUnbalance |
0 |
229 |
CN_BOOL |
|
1 |
230 |
CN_INT64 |
Ventilation Constraints Bitset |
See calculate_airflow_constraints() |
256 |
CN_UINT8 |
|
1=basic, 2=advanced, 3=installer |
257 |
CN_UINT8 |
|
|
274 |
CN_INT16 |
Temperature: Extract Air |
value in °C (171 -> 17.1 °C) |
275 |
CN_INT16 |
Temperature: Exhaust Air |
value in °C (86 -> 8.6 °C) |
276 |
CN_INT16 |
Temperature: Outdoor Air |
value in °C (60 -> 6.0 °C) |
277 |
CN_INT16 |
?? Temperature: Outdoor Air (Preheated?) |
value in °C (60 -> 6.0 °C) |
278 |
CN_INT16 |
?? Temperature: Supply Air (Preheated?) |
value in °C (184 -> 18.4 °C) |
290 |
CN_UINT8 |
Humidity: Extract Air |
value in % (49%) |
291 |
CN_UINT8 |
Humidity: Exhaust Air |
value in % (87%) |
292 |
CN_UINT8 |
Humidity: Outdoor Air |
value in % (67%) |
293 |
CN_UINT8 |
Humidity: Preheated Outdoor Air |
value in % (67%) |
294 |
CN_UINT8 |
Humidity: Supply Air |
value in % (35%) |
321 |
CN_UINT16 |
|
3 |
325 |
CN_UINT16 |
?? COMFOCOOLOFF |
0, 1, 3 |
328 |
CN_UINT16 |
?? MANUALMODE |
|
330 |
CN_UINT16 |
|
0, 1 |
337 |
CN_UINT32 |
?? PRESET |
0, 2, 32, 34 |
338 |
CN_UINT32 |
Bypass Override |
0=auto, 2=overriden |
341 |
CN_UINT32 |
?? COMFOCOOLOFF |
00000000, 02000000 |
342 |
CN_UINT32 |
Supply Fan Mode |
0 = balanced, 2 = supply only |
343 |
CN_UINT32 |
Exhaust Fan Mode |
0 = balanced, 2 = exhaust only |
344 |
CN_UINT32 |
?? MANUAL MODE |
|
345 |
CN_UINT32 |
|
0 |
346 |
CN_UINT32 |
|
0 |
369 |
CN_UINT8 |
Analog Input 0-10V 1 |
0 |
370 |
CN_UINT8 |
Analog Input 0-10V 2 |
0 |
371 |
CN_UINT8 |
Analog Input 0-10V 3 |
0 |
372 |
CN_UINT8 |
Analog Input 0-10V 4 |
0 |
384 |
CN_INT16 |
|
0.0 |
386 |
CN_BOOL |
|
0 |
400 |
CN_INT16 |
|
0.0 |
401 |
CN_UINT8 |
|
0 |
402 |
CN_BOOL |
?? PostHeaterPresent |
0 |
416 |
CN_INT16 |
ComfoFond Outdoor Air Temperature |
-40.0 |
417 |
CN_INT16 |
ComfoFond Ground Temperature |
10.0 |
418 |
CN_UINT8 |
ComfoFond GHE State Percentage |
0 |
419 |
CN_BOOL |
ComfoFond GHE Present |
0=absent, 1=present |
513 |
CN_UINT16 |
|
|
514 |
CN_UINT16 |
|
|
515 |
CN_UINT16 |
|
|
516 |
CN_UINT16 |
|
|
517 |
CN_UINT8 |
|
|
518 |
CN_UINT8 |
|
|
519 |
CN_UINT8 |
|
|
520 |
CN_UINT8 |
|
|
521 |
CN_INT16 |
|
|
522 |
CN_INT16 |
|
|
523 |
CN_INT16 |
|
|
524 |
CN_UINT8 |
|
|
784 |
CN_UINT8 |
ComfoCool State |
0=off, 1=on (0) |
785 |
CN_BOOL |
?? ComfoCoolCompressor State |
0 |
801 |
CN_INT16 |
?? T10ROOMTEMPERATURE |
0.0 |
802 |
CN_INT16 |
ComfoCool Condensor Temperature |
0.0 |
803 |
CN_INT16 |
?? T23SUPPLYAIRTEMPERATURE |
0.0 |
1024 |
CN_UINT16 |
|
|
1025 |
CN_UINT16 |
|
|
1026 |
CN_UINT16 |
|
|
1027 |
CN_UINT16 |
|
|
1028 |
CN_UINT16 |
|
|
1029 |
CN_UINT16 |
|
|
1030 |
CN_UINT16 |
|
|
1031 |
CN_UINT16 |
|
|
1056 |
CN_INT16 |
|
|
1124 |
CN_INT16 |
|
|
1125 |
CN_INT16 |
|
|
1126 |
CN_INT16 |
|
|
1127 |
CN_INT16 |
|
|
1281 |
CN_UINT16 |
|
|
1282 |
CN_UINT16 |
|
|
1283 |
CN_UINT16 |
|
|
1284 |
CN_UINT16 |
|
|
1285 |
CN_UINT16 |
|
|
1286 |
CN_UINT16 |
|
|
1287 |
CN_UINT16 |
|
|
1288 |
CN_UINT16 |
|
|
1297 |
CN_BOOL |
|
|
1298 |
CN_BOOL |
|
|
1299 |
CN_BOOL |
|
|
1300 |
CN_BOOL |
|
|
1301 |
CN_BOOL |
|
|
1302 |
CN_BOOL |
|
|
1303 |
CN_BOOL |
|
|
1304 |
CN_BOOL |
|
|