@@ -0,0 +1,224 @@ | ||
# Anvil Model | ||
|
||
Simengine can support various topology layouts; In this section we will attempt to model [alteeve’s](https://www.alteeve.com/c/) high-availability system called *Anvil* which consists of 2 striker dashboard machines, 2 target servers with IPMI interface, 2 PDUs, 2 Switches and 2 UPSes. High-level system map can be found on alteeve’s wiki [page](https://www.alteeve.com/w/Build_an_m2_Anvil!#Logical_Map.3B_Hardware_And_Plumbing). | ||
|
||
This table summarises the general layout of the `simengine` system model we are going to configure: | ||
|
||
| **key** | **Name** | **Type** | **Interface** | | ||
| ------- | ------------ | ---------- | ---------------------------------------------------- | | ||
| 1 | outlet-1 | outlet | | | ||
| 2 | outlet-2 | outlet | | | ||
| 3 | ups01 | ups | SNMP → reachable at 192.168.124.3 (default port 161) | | ||
| 4 | ups02 | ups | SNMP → reachable at 192.168.124.4 | | ||
| 5 | pdu01 | pdu | SNMP → reachable at 192.168.124.5 | | ||
| 6 | pdu02 | pdu | SNMP → reachable at 192.168.124.3 | | ||
| 7 | an-a01n01 | server-bmc | IPMI → reachable at localhost:9001 (or from the VM) | | ||
| 8 | an-a01n02 | server-bmc | IPMI → reachable at localhost:9101 (or from the VM) | | ||
| 9 | an-striker01 | server | | | ||
| 10 | an-striker02 | server | | | ||
|
||
4 VMs will be running so the host machine should preferably have more than 4 cores. | ||
|
||
|
||
![](https://d2mxuefqeaa7sj.cloudfront.net/s_C5C75BF29B870479D1EC95201C69BB583A74A130BB1FC9890A125939ED904715_1534526372651_Screenshot+from+2018-08-17+13-15-48.png) | ||
|
||
|
||
|
||
# Setup | ||
## Network Configuration | ||
|
||
We will need to allocate IP addresses for the SNMP simulators on the host machine (machine that will run `simengine`). In this example, we will temporarily add IP addresses to the existing `enp4s0` interface: | ||
|
||
|
||
sudo ip addr add dev enp4s0 192.168.124.3/24 # UPS 1 | ||
sudo ip addr add dev enp4s0 192.168.124.4/24 # UPS 2 | ||
sudo ip addr add dev enp4s0 192.168.124.5/24 # PDU 1 | ||
sudo ip addr add dev enp4s0 192.168.124.6/24 # PDU 2 | ||
|
||
**Note** that you may need to re-configure your firewall and expose port 161 to the striker systems. | ||
|
||
## VM | ||
|
||
4 VMs will be managed by the simulation engine — `an-a01n01` & `an-a01n02` will be running Fedora 28 and striker dashboards (`an-striker01` & `an-striker02`) will be hosted on CentOS-based system. | ||
|
||
The installation of the VMs plus minor setup need to be performed prior to the system modelling stage. | ||
|
||
**BMC** | ||
|
||
Since 2 VMs ( `an-a01n01` & `an-a01n02` ) will support BMC/IPMI interface, we will need to have lanplus interface and qemu options configured; | ||
|
||
Once you install the target operating systems, shut down the VMs and configure `.xml` args as following: | ||
|
||
**an-a01n01** | ||
|
||
Update `.xml` configurations: | ||
|
||
`sudo virsh edit an-a01n01` | ||
|
||
You will need to change the top-level tag to `<domain type='kvm' xmlns:qemu='http://libvirt.org/schemas/domain/qemu/1.0'>` and also add `qemu` command line arguments (after `</devices>`): | ||
|
||
|
||
<qemu:commandline> | ||
<qemu:arg value='-chardev'/> | ||
<qemu:arg value='socket,id=ipmi0,host=localhost,port=9002,reconnect=10'/> | ||
<qemu:arg value='-device'/> | ||
<qemu:arg value='ipmi-bmc-extern,id=bmc0,chardev=ipmi0'/> | ||
<qemu:arg value='-device'/> | ||
<qemu:arg value='isa-ipmi-bt,bmc=bmc0'/> | ||
<qemu:arg value='-serial'/> | ||
<qemu:arg value='mon:tcp::9012,server,telnet,nowait'/> | ||
</qemu:commandline> | ||
|
||
**an-a01n02** | ||
|
||
Almost identical steps need to be performed for the second VM (note that ipmi socket is assigned a different port this time `port=9102` which we will later pass as one of the command line arguments to `simengine-cli`). | ||
|
||
`sudo virsh edit an-a01n02` | ||
|
||
Change the top-level tag to `<domain type='kvm' xmlns:qemu='http://libvirt.org/schemas/domain/qemu/1.0'>` , add `qemu` command line arguments (after `</devices>`) as following: | ||
|
||
|
||
<qemu:commandline> | ||
<qemu:arg value='-chardev'/> | ||
<qemu:arg value='socket,id=ipmi0,host=localhost,port=9102,reconnect=10'/> | ||
<qemu:arg value='-device'/> | ||
<qemu:arg value='ipmi-bmc-extern,id=bmc0,chardev=ipmi0'/> | ||
<qemu:arg value='-device'/> | ||
<qemu:arg value='isa-ipmi-bt,bmc=bmc0'/> | ||
<qemu:arg value='-serial'/> | ||
<qemu:arg value='mon:tcp::9012,server,telnet,nowait'/> | ||
</qemu:commandline> | ||
# System Model | ||
|
||
At this stage, we should be ready to model our HA topology. You will need to drop the existing model in case the data store is not empty: | ||
|
||
`simengine-cli model drop` | ||
|
||
And pause the engine daemon: | ||
|
||
`sudo systemctl stop simengine-core` | ||
|
||
Running the source code below should re-create the Anvil topology; `model create` will add new assets to the data store & `model power-link` will link assets together: | ||
|
||
|
||
|
||
# Create 2 outlets, one powers 'an-ups01' another one powers 'an-ups02' | ||
simengine-cli model create outlet --asset-key=1 | ||
simengine-cli model create outlet -k2 | ||
|
||
# Add 2 UPSs | ||
simengine-cli model create ups -k=3 --name=an-ups01 --host=192.168.124.3 --port=161 | ||
simengine-cli model create ups -k=4 --name=an-ups02 --host=192.168.124.4 --port=161 | ||
|
||
# Create 2 PDUs | ||
simengine-cli model create pdu -k=5 -n=an-pdu01 --host=192.168.124.5 --port=161 | ||
simengine-cli model create pdu -k=6 -n=an-pdu02 --host=192.168.124.6 --port=161 | ||
|
||
# Add 2 Servers | ||
simengine-cli model create server-bmc -k=7 --domain-name=an-a01n01 --power-consumption=360 --psu-num=2 --psu-load 0.5 0.5 | ||
simengine-cli model create server-bmc -k=8 --domain-name=an-a01n02 --power-consumption=360 --psu-num=2 --psu-load 0.5 0.5 --port=9101 --vmport=9102 | ||
|
||
# Add 2 Striker Servers | ||
simengine-cli model create server -k=9 --domain-name=an-striker01 --power-consumption=240 --psu-num=1 | ||
simengine-cli model create server -k=10 --domain-name=an-striker02 --power-consumption=240 --psu-num=1 | ||
|
||
### Power Components | ||
# connect outlets & UPSs | ||
simengine-cli model power-link -s1 -d3 # {_Mains_}==>[an-ups01] | ||
simengine-cli model power-link -s2 -d4 # {_Mains_}==>[an-ups02] | ||
|
||
# connect ups & pdus | ||
simengine-cli model power-link -s31 -d5 # [an-ups01]==>[an-pdu01] | ||
simengine-cli model power-link -s41 -d6 # [an-ups02]==>[an-pdu02] | ||
|
||
# Power up servers | ||
simengine-cli model power-link -s51 -d72 # [an-pdu01]={port-1}=>{psu-2}=>[an-a01n01] | ||
simengine-cli model power-link -s52 -d82 # [an-pdu01]={port-2}=>{psu-2}=>[an-a01n02] | ||
|
||
simengine-cli model power-link -s61 -d71 # [an-pdu02]={port-1}=>{psu-1}=>[an-a01n01] | ||
simengine-cli model power-link -s62 -d81 # [an-pdu02]={port-2}=>{psu-1}=>[an-a01n02] | ||
|
||
# Power Up Striker Servers | ||
simengine-cli model power-link -s58 -d91 # [an-pdu01]={port-1}=>{psu-2}=>[an-a01n01] | ||
simengine-cli model power-link -s68 -d101 # [an-pdu02]={port-1}=>{psu-1}=>[an-a01n01] | ||
|
||
|
||
|
||
Re-start the daemon: | ||
`sudo systemctl start simengine-core` | ||
|
||
You can verify that the simulators are running by issuing: | ||
`ps aux | grep snmpsimd # should show 4 instances` | ||
|
||
`ps aux | grep ipmi_sim # should show 2 instances` | ||
|
||
|
||
## First Run | ||
|
||
The front-end web-page will display assets overlaid on top of each other. You will need to position the assets in the preferred way and save their coordinates. | ||
|
||
Here’s one way to arrange the assets (sandwich arrangement): | ||
|
||
![](https://d2mxuefqeaa7sj.cloudfront.net/s_C5C75BF29B870479D1EC95201C69BB583A74A130BB1FC9890A125939ED904715_1534526372651_Screenshot+from+2018-08-17+13-15-48.png) | ||
|
||
|
||
Click on gear ⚙️ icon & choose ‘Save Layout’; | ||
|
||
![](https://d2mxuefqeaa7sj.cloudfront.net/s_C5C75BF29B870479D1EC95201C69BB583A74A130BB1FC9890A125939ED904715_1534526478583_s.png) | ||
|
||
# Management | ||
|
||
**UPS** | ||
|
||
UPSes’ SNMP interface can be reached at `192.168.124.3` & `192.168.124.4` | ||
|
||
For example: | ||
|
||
`snmpwalk -Cc -c public -v 1 192.168.124.3 .1.3.6.1.4.1.318.1.1.1.2.2` | ||
|
||
`snmpwalk -Cc -c public -v 1 192.168.124.4 .1.3.6.1.4.1.318.1.1.1.2.2` | ||
|
||
More documentation on UPS management can be found here: [link](https://simengine.readthedocs.io/en/latest/AssetsConfigurations/#ups); | ||
|
||
|
||
**PDU** | ||
|
||
PDUs SNMP interface is accessible at `192.168.124.5` & `192.168.124.6` | ||
|
||
For example: | ||
|
||
`snmpwalk -Cc -c public -v 1 192.168.124.5` | ||
|
||
`snmpwalk -Cc -c public -v 1 192.168.124.6` | ||
|
||
**Server-BMC** | ||
|
||
Servers that support BMC interface can be accessed from both host machine & the VMs: | ||
|
||
Running from host example: | ||
|
||
`ipmitool -H localhost -p 9001 -U ipmiusr -P test sdr list # server 7 (an-a01n01)` | ||
|
||
`ipmitool -H localhost -p 9101 -U ipmiusr -P test sdr list # server 8 (an-a01n02)` | ||
|
||
VM: | ||
|
||
`sudo ipmitool sdr list` | ||
|
||
**Power Management** | ||
You can retrieve status of individual assets by issuing: | ||
|
||
`simengine-cli status -k1 # is out-1 up?` | ||
|
||
And power them up/down: | ||
|
||
`simengine-cli power down -k1 # out-1 is down` | ||
|
||
More docs can be found here: [link](https://simengine.readthedocs.io/en/latest/PowerManagement/), see `simengine-cli status -h` and `simengine-cli power -h` | ||
|
||
**Model Updates** | ||
You can update the existing model (for example, update UPS snmp ip address or server’s power consumption); | ||
|
||
**Note** that any model changes require `simengine-core` service restart; | ||
|
||
see `simengine-cli model update` for more information; |