Skip to content

Unprotected transport of credentials vulnerability in...

High severity Unreviewed Published Dec 25, 2021 to the GitHub Advisory Database • Updated Feb 3, 2023

Package

No package listedSuggest a package

Affected versions

Unknown

Patched versions

Unknown

Description

Unprotected transport of credentials vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from the communication between the PLC and the software. As a result, the complete access privileges to the PLC Web server may be obtained, and manipulation of the PLC output and/or suspension of the PLC may be conducted.

References

Published by the National Vulnerability Database Dec 24, 2021
Published to the GitHub Advisory Database Dec 25, 2021
Last updated Feb 3, 2023

Severity

High

EPSS score

0.077%
(35th percentile)

Weaknesses

CVE ID

CVE-2021-20826

GHSA ID

GHSA-v3cv-2j8p-p6xh

Source code

No known source code

Dependabot alerts are not supported on this advisory because it does not have a package from a supported ecosystem with an affected and fixed version.

Learn more about GitHub language support

Loading Checking history
See something to contribute? Suggest improvements for this vulnerability.