TEC Heat pump

Information about the TEC QRS11 heat pump and it's modbus connection. Not all values are know yet. USE AT YOUR OWN RISK.

Wordlist

Some words are shortend to make it easer to read, here is the list of word

  • Domestic Hot Water (DHW)

RS-485 (modbus)

Type Value
Baudrate 9600
Databits 8
Stopbits 2
Parity even

Discrete output (coil / read-write)

Address Parameter Value
1 DI4 AC Switch
2 DI5 DHW Switch
3 TR12 SG Function

Discrete input (read-only)

Address Parameter Value
1 AL01 Alarm: Low pressure
2 AL02 Alarm: High pressure
3 AL03 Alarm: Low outlet water temperature (ST < AR01)
5 AL05 Alarm: High outlet water temperature (ST > AR03)
6 AL17 Alarm: Water flow is short
7 AL18 Alarm: Low pressure alarms times within 24 hours is over the limit
8 AL19 Alarm: High pressure alarms times within 24 is over the limit
9 AL20
10 AL21
11 AL24
13 AL37
14 AL38
15 AL71
16 AL72
17 AL73
18 AL74
19 AL75
20 AL76
23 AL78
25 Secondary Pump
27 Primary Pump
32 NO4 AC Heater
33 D07 Crankshaft heater
34 NO1 DHW Circulation Pump
36 NO8 DHW Heater
39 NO6 Gas boiler

Input register (read-only)

Address Parameter Value unit
1 B1 Inlet Temperature 0.1°C
2 B2 Outlet Temperature 0.1°C
3 T2 Ambient Temperature 0.1°C
4 T4 Suction 0.1°C
5 T3 Discharge 0.1°C
6 B6 Low Pressure Side 0.1 bar
7 B7 High Pressure Side 0.1 bar
8 Flow 0.1 m3/h
9 Room Temperature 0.1°C
13 Compressor 1 Hz
14 Y3 Indoor pump PWM 0.1%
17 B4 Hot Water 0.1°C
18 Operating Hours 1 Hour
20 Unit State unit_state
22 Produced heat kWh
23 Energy consumed kWh

Holding Register (read-write)

Address Parameter Value default min max unit Access
9 Room Temperature 0.1°C
61 ST01 Temperature on cooling mode 13 ST11 ST12 0.1°C User
62 ST02 Temperature on heating mode 35 ST13 ST14 0.1°C User
63 ST03 Temperature difference on cooling mode 1 1 10 0.1°C User
64 ST04 Temperature difference on heating mode 1 1 10 0.1°C User
65 ST06 Compensation factor for heating curve 0.6 0 3 0.1 User
66 ST07 Ambient temperature condition for starting aux heat 0 -10 20 0.1°C User
67 ST08 Compensation factor for cooling curve 0.6 0 3 0.1 User
68 ST11 Minimum settable cooling temperature 12 0 ST12 0.1°C Manufacturer
69 ST12 Maximum settable cooling temperature 40 ST11 60 0.1°C Manufacturer
70 ST13 Minimum settable heating temperature 20 0 ST14 0.1°C Manufacturer
71 ST14 Maximum settable heating temperature 50 ST13 8 0.1°C Manufacturer
72 ST15 Minimum settable DHW temperature 20 0 ST16 0.1°C Manufacturer
73 ST16 Maximum settable DHW temperature 65 ST15 80 0.1°C Manufacturer
74 ST17 SG Function: Cooling/heating water temperature decrement/increment 2 1 10 0.1°C User
75 ST18 SG Function: DHW temperature increment 5 1 10 0.1°C User
77 ST33 DHW circulation pump off interval 15 0 180 1 min User
78 ST34 DHW circulation pump running time 3 0 180 1 min User
79 ST09 DHW temperature setup 50 ST15 ST16 0.1°C User
80 ST10 DHW temperature difference setup 3 1 10 0.1°C User

Convertion Tables

unit_state

value state
1 Heating
2 Cooling
3 antifreeze
4 Defrost
5 Standby
6 Off
7 Starting
8 On
9 DHW