384 bug voltage drop should be considered when selecting cable to connect new components #411

Conversation

joda9
Copy link
Collaborator

@joda9 joda9 commented Jul 22, 2024

Description

Add function to validate voltage drop against maximum allowable limits in cable selection

  • Implemented a new function to check if the voltage difference exceeds the maximum allowed voltage drop.
  • Tested the function for both low voltage (LV) and medium voltage (MV) scenarios.
  • Added limits for mv and lv grids

Fixes #384

Type of change

Please delete options that are not relevant.

  • Bug fix (non-breaking change which fixes an issue)
  • New feature (non-breaking change which adds functionality)
  • Breaking change (fix or feature that would cause existing functionality to not work as expected)

Checklist:

  • New and adjusted code is formatted using the pre-commit hooks
  • New and adjusted code includes type hinting now
  • I have commented my code, particularly in hard-to-understand areas
  • I have made corresponding changes to the documentation
  • I have added tests that prove my fix is effective or that my feature works
  • New and existing unit tests pass locally with my changes
  • The Read the Docs documentation is compiling correctly
  • If new packages are needed, I added them the setup.py, and if needed the rtd_requirements.txt, the eDisGo_env.yml and the eDisGo_env_dev.yml.
  • I have added new features to the corresponding whatsnew file

@@ -50,6 +50,11 @@ upper_limit_voltage_level_6 = 0.2
upper_limit_voltage_level_5 = 5.5
upper_limit_voltage_level_4 = 20.0

lv_max_voltage_deviation = 0.03
# from VDE-AR-N 4100 (VDE-AR-N 4100) Anwendungsregel: 2019-04
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Can you please add the comment above the value it applies to?

s_max : float or array-like
Apparent power the cable must carry in MVA.
r_total : float or array-like
Total resistance in Ohms.
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Please add "of the line" here, as well as for x_total and v_nom.

sin_phi = np.sqrt(1 - cos_phi**2)
# Calculate the voltage difference using the formula from VDE-AR-N 4105
voltage_diff = np.abs(
(s_max * 1e6 / (v_nom * 1e3)) * (r_total * cos_phi + sign * x_total * sin_phi)
Copy link
Collaborator

@birgits birgits Jul 30, 2024

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Please avoid multiplying and dividing unnecessarily due to rounding errors. 1e6/1e3/1e3 all cancels out, so it is not necessary here.

Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Also, please don't return the absolute value here because it would be better to test, whether the voltage rises or drops.

length : float
Length of the cable in km. Default: 0.
max_voltage_diff : float
Maximum voltage difference in pu. Default: None.
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Please elaborate this a bit more. It is the maximum allowed voltage difference over the line that connects the new component to the grid. If it is not specified, it is taken from the config files (section grid_connection, parameters lv_max_voltage_deviation and mv_max_voltage_deviation).

return voltage_difference_pu


def select_cable(
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Please adapt the docstring of this function. The cable is not only selected based on the apparent power anymore but also considering the voltage deviation over the cable. The docstring should always start with a short one line description and then in the next paragraph it can be elaborated if needed.

length: float = 0,
max_voltage_diff: float | None = None,
max_cables: int = 7,
cos_phi: float | None = 0.95,
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Please rename this parameter to power_factor to have it consistent with the rest of the code base. Also, I would prefer that there is no default value but that the default value is obtained from the configs. For this, the type of the component to be connected needs to be specified as input parameter.

max_voltage_diff: float | None = None,
max_cables: int = 7,
cos_phi: float | None = 0.95,
inductive_reactance: bool = True,
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Please use "reactive_power_mode" instead of "inductive_reactance" to have it consistent with the rest of the code base, e.g. here). Also, whether the reactive power is positive or negative in case of inductive behavior depends on the sign convention used. In eDisGo we use the generator sign convention for generators and storage units and the load sign convention for loads. This also needs to be fixed in the other functions.

cable_count = 1

if not cos_phi:
cos_phi = 0.95
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

This is not necessary because 0.95 is already the default value in the function head.

@birgits birgits merged commit 1c59309 into dev Aug 8, 2024
8 checks passed
@birgits birgits deleted the 384-bug-voltage-drop-should-be-considered-when-selecting-cable-to-connect-new-components branch September 13, 2024 07:18
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
None yet
Projects
None yet
Development

Successfully merging this pull request may close these issues.

[BUG] Voltage drop should be considered when selecting cable to connect new components
2 participants