Skip to content

Commit

Permalink
apcups plugin: add user_doc, remove Readme.md
Browse files Browse the repository at this point in the history
  • Loading branch information
bmxp committed Sep 6, 2023
1 parent e60c119 commit 923fef4
Showing 1 changed file with 334 additions and 0 deletions.
334 changes: 334 additions & 0 deletions apcups/user_doc.rst
Original file line number Diff line number Diff line change
@@ -0,0 +1,334 @@
.. index:: Plugins; apcups
.. index:: apcups


===============================
apcups
===============================


.. image:: webif/static/img/plugin_logo.png
:alt: plugin logo
:width: 300px
:height: 300px
:scale: 50 %
:align: left

<Hier erfolgt die allgemeine Beschreibung des Zwecks des Plugins>


Anforderungen
=============

Ein laufender ``apcupsd`` mit einem konfigurierten Netserver (NIS) ist notwendig. Dieser kann lokal oder remote laufen.
Das Plugin fragt Laufzeitdaten vom apcupsd über das Hilfsprogramm ``apcaccess`` ab. Aus diesem Grund muss das ``apcups`` Package auch lokal installiert sein.
Wenn der Daemon lokal installiert ist, sollte die Datei ``/etc/apcupsd/apcupsd.conf`` noch folgende Informationen beinhalten:

::

NETSERVER on
NISPORT 3551
NISIP 127.0.0.1

Unterstützte Geräte
-------------------

Aollte mit allen APC UPS Geräten funktionieren die den apcupsd unterstützen. Getestet wurde nur mit einer **smartUPS**.


Konfiguration
=============

Die Plugin Parameter und die Informationen zur Item-spezifischen Konfiguration des Plugins sind
unter :doc:`/plugins_doc/config/apcups` beschrieben.


plugin.yaml
-----------

Zu den Informationen, welche Parameter in der ../etc/plugin.yaml konfiguriert werden können bzw. müssen, bitte
bitte die Dokumentation :doc:`Dokumentation </plugins_doc/config/apcups>` lesen, die aus
den Metadaten der plugin.yaml erzeugt wurde (siehe oben).

items.yaml
----------

Zu den Informationen, welche Attribute in der Item Konfiguration verwendet werden können bzw. müssen, bitte
bitte die Dokumentation :doc:`Dokumentation </plugins_doc/config/apcups>` lesen, die aus
den Metadaten der plugin.yaml erzeugt wurde (siehe oben).

Es gibt nur ein einziges Attribut ``apcups``. Die Namen für den Statusabruf können über den Befehl ``apcaccess`` auf der Kommandozeile
abgerufen werden. Damit wird eine Liste der Art ``Statusname : Wert`` angezeigt.

Der Wert der dem ``apcups`` Item Attribut als Parameter übergeben wird ist dieser Statusname. Dem Item wird dann dieser Wert zugewiesen.

::

APC : 001,050,1127
DATE : 2017-11-02 07:59:15 +0100
HOSTNAME : sh11
VERSION : 3.14.12 (29 March 2014) debian
UPSNAME : UPS_IDEN
CABLE : Ethernet Link
DRIVER : PCNET UPS Driver
UPSMODE : Stand Alone
STARTTIME: 2017-11-02 07:59:11 +0100
MODEL : Smart-UPS 1400 RM
STATUS : ONLINE
LINEV : 227.5 Volts
LOADPCT : 31.2 Percent
BCHARGE : 100.0 Percent
TIMELEFT : 30.0 Minutes
MBATTCHG : 10 Percent
MINTIMEL : 5 Minutes
MAXTIME : 0 Seconds
MAXLINEV : 227.5 Volts
MINLINEV : 226.0 Volts
OUTPUTV : 227.5 Volts
SENSE : High
DWAKE : 0 Seconds
DSHUTD : 120 Seconds
DLOWBATT : 2 Minutes
LOTRANS : 208.0 Volts
HITRANS : 253.0 Volts
RETPCT : 0.0 Percent
ITEMP : 25.6 C
ALARMDEL : Low Battery
BATTV : 27.7 Volts
LINEFREQ : 49.8 Hz
LASTXFER : Line voltage notch or spike
NUMXFERS : 0
TONBATT : 0 Seconds
CUMONBATT: 0 Seconds
XOFFBATT : N/A
SELFTEST : NO
STESTI : 336
STATFLAG : 0x05000008
REG1 : 0x00
REG2 : 0x00
REG3 : 0x00
MANDATE : 08/16/00
SERIALNO : GS0034003173
BATTDATE : 06/20/15
NOMOUTV : 230 Volts
NOMBATTV : 24.0 Volts
EXTBATTS : 0
FIRMWARE : 162.3.I
END APC : 2017-11-02 08:00:39 +0100

Das Plugin führt eine automatische Typumwandlung durch entsprechend dem verwendeten Item Typ.
Bei der Umwandlung in einen numerischen Wert wird nach dem ersten Leerzeichen abgeschnitten und dann konvertiert.
Aus ``235 Volt`` wird also ``235``

logic.yaml
----------

Zu den Informationen, welche Konfigurationsmöglichkeiten für Logiken bestehen, bitte
bitte die Dokumentation :doc:`Dokumentation </plugins_doc/config/apcups>` lesen, die aus
den Metadaten der plugin.yaml erzeugt wurde (siehe oben).

Funktionen
----------

Zu den Informationen, welche Funktionen das Plugin bereitstellt (z.B. zur Nutzung in Logiken), bitte
bitte die Dokumentation :doc:`Dokumentation </plugins_doc/config/apcups>` lesen, die aus
den Metadaten der plugin.yaml erzeugt wurde (siehe oben).

<Hier können bei Bedarf ausführliche Beschreibungen zu den Funktionen dokumentiert werden.>

|
Beispiele
=========

Beispiel
~~~~~~~

The example below will read the keys **LINEV**, **STATUS** and
**TIMELEFT** and returns their values.

.. code:: yaml
# items/apcups.yaml
serverroom:
apcups:
linev:
visu_acl: ro
type: num
apcups: linev
status:
# will be 'ONLINE', 'ONBATT', or in case of a problem simply empty
visu_acl: ro
type: str
apcups: status
timeleft:
visu_acl: ro
type: num
apcups: timeleft
**type** depends on the values.

Status Report Fields
~~~~~~~~~~~~~~~~~~~~

Due to a look into this
http://apcupsd.org/manual/manual.html#configuration-examples file the
meaning of the above variables are as follows

::

APC
Header record indicating the STATUS format revision level, the number of records that follow the APC statement, and the number of bytes that follow the record.
DATE
The date and time that the information was last obtained from the UPS.
HOSTNAME
The name of the machine that collected the UPS data.
UPSNAME
The name of the UPS as stored in the EEPROM or in the UPSNAME directive in the configuration file.
VERSION
The apcupsd release number, build date, and platform.
CABLE
The cable as specified in the configuration file (UPSCABLE).
MODEL
The UPS model as derived from information from the UPS.
UPSMODE
The mode in which apcupsd is operating as specified in the configuration file (UPSMODE)
STARTTIME
The time/date that apcupsd was started.
STATUS
The current status of the UPS (ONLINE, ONBATT, etc.)
LINEV
The current line voltage as returned by the UPS.
LOADPCT
The percentage of load capacity as estimated by the UPS.
BCHARGE
The percentage charge on the batteries.
TIMELEFT
The remaining runtime left on batteries as estimated by the UPS.
MBATTCHG
If the battery charge percentage (BCHARGE) drops below this value, apcupsd will shutdown your system. Value is set in the configuration file (BATTERYLEVEL)
MINTIMEL
apcupsd will shutdown your system if the remaining runtime equals or is below this point. Value is set in the configuration file (MINUTES)
MAXTIME
apcupsd will shutdown your system if the time on batteries exceeds this value. A value of zero disables the feature. Value is set in the configuration file (TIMEOUT)
MAXLINEV
The maximum line voltage since the UPS was started, as reported by the UPS
MINLINEV
The minimum line voltage since the UPS was started, as returned by the UPS
OUTPUTV
The voltage the UPS is supplying to your equipment
SENSE
The sensitivity level of the UPS to line voltage fluctuations.
DWAKE
The amount of time the UPS will wait before restoring power to your equipment after a power off condition when the power is restored.
DSHUTD
The grace delay that the UPS gives after receiving a power down command from apcupsd before it powers off your equipment.
DLOWBATT
The remaining runtime below which the UPS sends the low battery signal. At this point apcupsd will force an immediate emergency shutdown.
LOTRANS
The line voltage below which the UPS will switch to batteries.
HITRANS
The line voltage above which the UPS will switch to batteries.
RETPCT
The percentage charge that the batteries must have after a power off condition before the UPS will restore power to your equipment.
ITEMP
Internal UPS temperature as supplied by the UPS.
ALARMDEL
The delay period for the UPS alarm.
BATTV
Battery voltage as supplied by the UPS.
LINEFREQ
Line frequency in hertz as given by the UPS.
LASTXFER
The reason for the last transfer to batteries.
NUMXFERS
The number of transfers to batteries since apcupsd startup.
XONBATT
Time and date of last transfer to batteries, or N/A.
TONBATT
Time in seconds currently on batteries, or 0.
CUMONBATT
Total (cumulative) time on batteries in seconds since apcupsd startup.
XOFFBATT
Time and date of last transfer from batteries, or N/A.
SELFTEST

The results of the last self test, and may have the following values:

OK: self test indicates good battery
BT: self test failed due to insufficient battery capacity
NG: self test failed due to overload
NO: No results (i.e. no self test performed in the last 5 minutes)

STESTI
The interval in hours between automatic self tests.
STATFLAG
Status flag. English version is given by STATUS.
DIPSW
The current dip switch settings on UPSes that have them.
REG1
The value from the UPS fault register 1.
REG2
The value from the UPS fault register 2.
REG3
The value from the UPS fault register 3.
MANDATE
The date the UPS was manufactured.
SERIALNO
The UPS serial number.
BATTDATE
The date that batteries were last replaced.
NOMOUTV
The output voltage that the UPS will attempt to supply when on battery power.
NOMINV
The input voltage that the UPS is configured to expect.
NOMBATTV
The nominal battery voltage.
NOMPOWER
The maximum power in Watts that the UPS is designed to supply.
HUMIDITY
The humidity as measured by the UPS.
AMBTEMP
The ambient temperature as measured by the UPS.
EXTBATTS
The number of external batteries as defined by the user. A correct number here helps the UPS compute the remaining runtime more accurately.
BADBATTS
The number of bad battery packs.
FIRMWARE
The firmware revision number as reported by the UPS.
APCMODEL
The old APC model identification code.
END APC
The time and date that the STATUS record was written.


|
Web Interface
=============

Aktuell hat das Plugin kein Webinterface

Tab 1: <Name des Tabs>
----------------------

<Hier wird der Inhalt und die Funktionalität des Tabs beschrieben.>

.. image:: assets/webif_tab1.jpg
:class: screenshot

<Zu dem Tab ist ein Screenshot im Unterverzeichnis ``assets`` des Plugins abzulegen.

|
Version History
===============

<In diesem Abschnitt kann die Versionshistorie dokumentiert werden, falls der Plugin Autor dieses möchte.
Diese Abschnitt ist optional.>


0 comments on commit 923fef4

Please sign in to comment.