This does not cover the PV naming convention, rather it covers the PVs you need to implement.
The PV naming conventions are described on the PV naming page.
-
For a slow changing value (e.g. a temperature), there needs to be a current value readback, a setpoint and a setpoint readback:
record(ai, "$(P)TEMPERATURE") { field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@devEuro.proto getCurrentTemp $(PORT)") field(PREC, "3") field(EGU, "K") } record(ao, "$(P)TEMPERATURE:SP") { field(DTYP, "stream") field(OUT, "@devEuro.proto setTempSetpoint $(PORT)") field(PREC, "3") field(EGU, "K") } record(ai, "$(P)TEMPERATURE:SP:RBV") { field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@devEuro.proto getTempSetpoint $(PORT)") field(PREC, "3") field(EGU, "K") }
-
For a value that changes instantly (e.g. a trigger level), there needs to be a current value readback, a setpoint and a setpoint readback. However the setpoint readback should be an alias for the readback:
record(ai, "$(P)TRIG_LVL") { field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@devHameg_8123.proto getTriggerLevel $(PORT)") field(PREC, "3") field(EGU, "V") } record(ao, "$(P:)TRIG_LVL:SP") { field(DTYP, "stream") field(OUT, "@devHameg_8123.proto setTriggerLevel $(PORT)") field(PREC, "3") field(EGU, "V") } alias("$(P)TRIG_LVL", "$(P)TRIG_LVL:SP:RBV")
-
For a toggle-style button (e.g. voltage on/off) where the current setting can be read, use the same format as 2) but with binary records:
record(bi, "$(P)VOLTAGE_ON") { field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@devPSU.proto getVoltageOn $(PORT)") field(ZNAM, "OFF") field(ONAM, "ON") } record(bo, "$(P)VOLTAGE_ON:SP") { field(DTYP, "stream") field(OUT, "@devPSU.proto setVoltageOn $(PORT)") field(ZNAM, "OFF") field(ONAM, "ON") } alias("$(P)VOLTAGE_ON", "$(P)VOLTAGE_ON:SP:RBV")
-
For a toggle-style button where the current setting
cannot
be read or a push-style button (e.g. a reset button), there needs to be a setpoint and, for convenience, an alias for the current value. This allows the value to be set using either PV.record(bo, "$(P)RESET:SP") { field(DTYP, "stream") field(OUT, "@devMyDevice.proto reset $(PORT)") field(ZNAM, "YES") field(ONAM, "TRUE") } alias("$(P)RESET:SP", "$(P)RESET")
-
A read-only value (e.g. a status string).
record(stringin, "$(P)STATUS") { field(DTYP, "stream") field(INP, "@devMyDevice.proto getStatus $(PORT)") field(SCAN, "1 second") }