This page contains information pertinent to the automation of the RIKEN Front End Beamline Control at ISIS.

Background

ISIS have taken over management of the RIKEN facility at ISIS. Various systems on the RIKEN facility are being upgraded over time.

Control System

Control of the RIKEN Front End hardware will be migrated to IBEX in a series of phases. Therefore, there will be a period of mixed operation, in which some devices will be controlled via the existing RIKEN control system and others are controlled by IBEX.

Timeline

Task/Event Date Notes
PSU control Summer 2018 Upgrade PSU control. See #2813, #3150.
ARGUS Magnets Summer 2018 Changes to ARGUS magnets (no further details).
Replace PLC Easter 2019 Preferred replacement PLC is a Schneider Modicon M580 - ePac.
Mitsubishi PSU No date yet Part of cryogenics system. May be controlled via its own dedicated PC.

Equipment

The table below captures what the Experiment Controls Group knows about the RIKEN Front End hardware (as of September 2018).

Manufacturer Model Type Connection Driver Notes
Danfysik XXXX PSU RS232 DFKPS see PSUs note
GEC XXXX PSU RS232 ??? see PSUs note
Schneider ???? PLC RS232 ModbusRTU PLC is, or is similar to, a Schneider Electric Quantum PLC.
Kicker ??? Currently not functional. No immediate plans to make it so.
Separator ??? Separator PSUs are due to be replaced (no timescale yet)
Pfeiffer TPG300 Vacuum Monitor RS232 TPG300 There are ~7 of these. Assumed to have RS232 cards.
Pfeiffer TCP350 Turbo Pump TCP/IP TCP350
National Instruments DAQmx Data Acquisition TCP/IP Used to communicate with PLC & PSUs
Note: PSUs
  1. The RIKEN PSUs are physically a mixture of Danfysik, GEC, and Japanese power supplies. However, they are all fitted with Danfysik control boards. So as far as IBEX is concerned they are all Danfysik devices.
  2. The Danfysik control boards talk a slightly different protocol than the other Danfysiks (as used on Muon-FE, EMU, LOQ and other instruments). For this reason, they require their own IOC. All of the power supplies on RIKEN-FE are controlled by a single IOC.
  3. We have no record of the actual Danfysik model number to which these boards correspond (it is quite possible that they don't correspond to any standard Danfysik), so we have no Danfysik manuals for these particular boards. The best we information we have is the documents stored in the RIKEN_power_supplies sub-folder in the Experiment Controls Group's Manuals share.