Notifications
You must be signed in to change notification settings - Fork 2
Running IOCs
Wiki > The Backend System > IOCs > Running IOCs
Either:
- start the IOC through the GUI.
- If this is a new IOC you will need to run
make iocstartups
in the EPICS folder for the IOC to be displayed in the GUI.
- If this is a new IOC you will need to run
- start the IOC through the console (ctrl + x)
- switch off/on auto start (ctrl + t)
- start the IOC by running
runIOC.bat st.cmd
(iniocBoot/Appdir
)
Open an epics terminal a list all running instruments with
console -M localhost -x
To interact with an IOC use
console -M localhost <IOC_NAME>
console will attempt to complete the name if you only give part of it and will give you possible options. Once in the console:
-
ctrl-x
: starts and stops the IOC -
crtl-e
c
.
: exits the console
TO switch an IOC to simulation mode the default is
caput <IOC PV NAME>:SIM 1
It is possible to set macros for an IOC either through the IBEX GUI or using the globals.txt file. Loaded in using icpconfig.
The globals.txt is file is held in C:\Instrument\Settings\config\NDW_____\configurations
. In here, global macros are set with <macro name>=<value>
, and macros specific for an IOC are set with <ioc name>__<macro name>=<value>
e.g.
GALIL_01__GALILADDR=130.246.51.169
GALIL_01__MTRCTRL=2
GALIL_03__MTRCTRL=3
GALIL_03__DEVSIM=1
EGXCOLIM_01__RECSIM=1
Use the following to read a waveform PV of a compressed hexed string
caget -t -S <PV NAME>|uzhex
(uzhex - think unzip hex)